BS 7671:2008

BS 7671:2008 was issued on 1st of January 2008 and is intended to come into effect on 1st of July 2008

  • News home
  • Access control systems
  • Building construction management
  • CCTV and security systems
  • CORGI gas service
  • Electrical testing
  • Facilities management
  • Fire alarm services
  • General building maintenance
  • Mechanical maintenance
  • Property management
 
  1. BS 7671:2008 was issued on 1st of January 2008 and is intended to come into effect on 1st of July 2008
  2. The Regulations apply to the design, erection and verification of electrical installations, also additions and alterations to existing installations.
  3. Existing installations that have installed in accordance with earlier edition of the Regulations may not comply with this edition in every respect. This does not necessarily mean that they are unsafe for continued use or require upgrading.
  4. BS 7671:2008 includes changes necessary to maintain technical alignment with CENELEC harmonisation documents

 

Purpose of Periodic Inspection

 

  1. “The main purpose of periodic inspection and testing is to detect so far as is reasonably practicable, and to report on, any factors impairing the safety of an electrical installation.”
  2. “Safety of persons and livestock against the effects of electric shock and burns.”
  3. “Protection against damage to property by fire and heat arising from an installation defect.”
  4. “Confirmation that the installation is not damaged or deteriorated so as to impair safety.”
  5. “Identification of installation defects and departures from the requirements of BS 7671 that may give rise of danger.”

 

Recommended Initial Frequencies of Inspection of electrical Installations

Type of installation

Routine check*

Maximum period between inspections and testing   as necessary

Reference
(see notes bellow)

General Installations

 

 

 

Domestic

 

Change of occupancy/ 10 years

1, 2

Commercial

1 year

Change of occupancy/ 5 years

1, 2

Educational establishments

4 months

5 years

1, 2

Hospitals

1 year

5 years

1, 2

Industrial

1 year

3 years

1

Residential accommodation

At change of occupancy/
1 year

5 years

1, 2

Offices

1 year

5 years

1, 2

Shops

1 year

5 years

1, 2

Laboratories

1 year

5 years

1, 2

Cinemas

 

Change of occupancy/ 10 years

2, 6

Church installations

1 year

Change of occupancy/ 5 years

2

Leisure complexes excluding swimming pools

1 year

5 years

1, 2, 6

Places of public entertainment

1 year

5 years

1, 2, 6

Restaurants and hotels

1 year

3 years

1, 2, 6

Theatres

1 year

5 years

2, 6, 7

Public houses

1 year

5 years

1, 2, 6

Village halls/ Community centres

1 year

5 years

1, 2

Intervals between periodic inspection and testing

The intervals between periodic inspection and testing will depend on number of considerations, including some or all of the factors indicated bellow, depending on the particular circumstances:

  1. Age of the installation (it may be reasonable to expect the intervals to become progressively shorter as the installation ages).
  2. Type of premises
  3. Environmental conditions (ie external influences).
  4. Normal life expectancy of the installation (eg vandalism).
  5. Changed usage of the premises (and the installation).
  6. The extend of any ware and tear, damage or other deterioration.

 

        Determination of the interval to the next inspection will always be a matter of engineering judgment to be exercised by the inspector.

 

              

  1. BS 7671:2008 requires that there are no code 1 and 2 and in some cases code 3 departures to the fixed electrical installation in order for the Report to class the installation as being in satisfactory serviceable condition.